DESCRIPTION
If the airflow from the front registers is weak regardless of the blower speed setting displayed on the air conditioning control assembly, the following factors may be the cause.
|
Symptom | Factor |
|---|---|
|
|
PROCEDURE
| 1. |
CHECK AIR CONDITIONING SYSTEM |
(a) Operate the blower switch with the following conditions met and check that the airflow volume changes.
|
Blower Speed | Condition |
|---|---|
|
LO → HI |
|
OK:
Airflow volume increases.
| NG | | GO TO OTHER DIAGNOSIS PROCEDURE (Blower Motor Circuit) |
|
| 2. |
CHECK CLEAN AIR FILTER |
(a) Visually check the clean air filter.
Click here
OK:
The clean air filter is not dirty or clogged.
| NG | | REPLACE CLEAN AIR FILTER |
|
| 3. |
CHECK NO. 1 COOLER THERMISTOR |
(a) Check the installation condition of the No. 1 cooler thermistor.
OK:
The No. 1 cooler thermistor is installed correctly.
| NG | | INSTALL NO. 1 COOLER THERMISTOR |
|
| 4. |
CHECK ASPIRATOR |
(a) Check the installation condition of the aspirator.
OK:
The aspirator is installed correctly.
| OK | | REPLACE HEATER RADIATOR UNIT SUB-ASSEMBLY OR NO. 1 COOLER EVAPORATOR SUB-ASSEMBLY |
| NG | | INSTALL ASPIRATOR |